Applications
Used as bare overhead conductor for primary and secondary distribution. Designed utilizing a high-strength aluminum alloy to achieve a high strength-to-weight ratio; affords better sag characteristics. Aluminum alloy gives AAAC higher resistance to corrosion than ACSR.

Construction
Standard 6201-T81 high strength aluminum conductors, conforming to ASTM Specification B-399, are concentric-lay- stranded, similar in construction and appearance to 1350 grade aluminum conductors. Standard 6201 alloy conductors are similar to other alloy conductors commercially known as Ardival, Aldrey or Almelec. They were developed to fill the need for an economical conductor for overhead applications requiring higher strength than that obtainable with 1350 grade aluminum conductors, but without a steel core. The DC resistance at 20°C of the 6201-T81 conductors and of the standard ACSRs of the same diameter are approximately the same. Conductors of the 6201-T81 alloys are harder and, therefore, have a greater resistance to abrasion than conductors of 1350-H19 grade aluminum.

Specifications
AAAC bare conductor meets or exceeds the following ASTM specifications :

B-398 Aluminum Alloy 6201-T81 Wire for Electrical Purposes
B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.

Notes
  • Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 52.5% IACS, AC resistance at 60Hz
  • Current ratings are based on 75oC conductor temperature, 25oC ambient, 2ft/s wind, 96/watts/sq.ft sun, 0.5 coefficients of emissivity and absorption.




  • Request InformationCompare Items   Results per Page : 
      Results 1 - 14 of 14 1 

    Item #

    Size KCM

    Strand

    Approx EC Cond. with Equivalent Resistance

    Stranding

    Diameter Indiv. Wire

    Diameter Complete Cable

    Cross Sectional Area

    Weight Per 1000ft

    Rated Breaking Strength

    Rating

    Akron 30.58 7/w 6 6/1 .0661 Inches .198 Inches .0240 sq.inches 28.7 Lbs 1110 Lbs 107 Amps
    Alton 48.69 7/w 4 6/1 .0834 Inches .250 Inches .0382 sq.inches 45.7 Lbs 1760 Lbs 143 Amps
    Ames 77.47 7/w 2 6/1 .1052 Inches .316 Inches .0608 sq.inches 72.7 Lbs 2800 Lbs 191 Amps
    Azusa 123.3 7/w 1/0 6/1 .1327 Inches .398 Inches .0968 sq.inches 115.7 Lbs 4460 Lbs 256 Amps
    Anaheim 155.4 7/w 2/0 6/1 .1490 Inches .447 Inches .1221 sq.inches 145.9 Lbs 5390 Lbs 296 Amps
    Amherst 195.7 7/w 3/0 6/1 .1672 Inches .502 Inches .1537 sq.inches 183.7 Lbs 6790 Lbs 342 Amps
    Alliance 246.9 7/w 4/0 6/1 .1878 Inches .563 Inches .1939 sq.inches 231.8 Lbs 8560 Lbs 395 Amps
    Butte 312.8 19/w 266.8 26/7 .1283 Inches .642 Inches .2456 sq.inches 293.6 Lbs 11000 Lbs 460 Amps
    Canton 394.5 19/w 336.4 26/7 .1441 Inches .721 Inches .3098 sq.inches 370.3 Lbs 13300 Lbs 532 Amps
    Cairo 465.4 19/w 397.5 26/7 .1565 Inches .783 Inches .3655 sq.inches 436.9 Lbs 15600 Lbs 590 Amps
    Darien 559.5 19/w 477.0 26/7 .1716 Inches .858 Inches .4394 sq.inches 525.2 Lbs 18800 Lbs 663 Amps
    Elgin 652.4 19/w 556.5 26/7 .1853 Inches .927 Inches .5124 sq.inches 612.4 Lbs 21900 Lbs 729 Amps
    Flint 740.8 37/w 636.0 26/7 .1415 Inches .991 Inches .5818 sq.inches 695.5 Lbs 24400 Lbs 790 Amps
    Greely 927.2 37/w 795.0 26/7 .1583 Inches 1.108 Inches .7282 sq.inches 870.4 Lbs 30500 Lbs 908 Amps
      Results 1 - 14 of 14 1